Total electric power required, P = 800 kW
supply voltage V = 220 volt
voltage at which electric plant generating power V1 = 440 volt
distance between town and power generating station, d = 15 km
total resistance of two wire cable R = (15+15) x 0.5 = 15 ohm
input voltage of transformer Vi = 4000 volt
output voltage of transformer Vo = 220 volt
current in wire line
total power supplied by the plant = 800 + 600 = 1400 KW

V3 and combination of V1 and V2 (V1 + V2) are connected in parallel so potential in V3 must be equal to potential in (V1 + V2)
the potential difference across AB = = +.